Fire Safety Certificate for Schools and Coaching Classes in Gujarat

Gujarat by building typeLast verified: 4 min read

In Gujarat, educational buildings of 9 m and above need a Fire Safety Certificate, and the renewal table names pre-schools, coaching classes and training centres above 9 m as well. Colleges, schools and hostels are all part of the picture. A Fire Safety Executive is required for educational buildings of 15 m and above or with more than 5,000 students.

Certificate needed
9 m and above
Renewal, 9 to 15 m
FSO General, Advanced or Specialist
Renewal, 15 to 30 m
FSO Advanced or Specialist
Fire Safety Executive
15 m and above, or over 5,000 students

Which education buildings are covered

The Third Schedule, as replaced on 23 October 2026, lists educational and institutional buildings from 9 m. The portal checklists split the category into buildings over 9 m and under 15 m, or with a floor over 500 m². The renewal table also names pre-schools, coaching classes and training centres above 9 m, so tuition classes are inside the system and not a loophole.

The National Building Code classes schools as Group B (B-1 for schools up to senior secondary with at least 20 students, B-2 for other training institutions with at least 100). Hostel or dormitory portions count as sleeping accommodation and are treated separately. Smaller premises can still be covered through other categories, so check the portal checklist for your exact use.

See who needs a fire safety certificate in Gujarat for the full Schedule.

Building and escape rules schools are checked against

The GIDM handbook for educational buildings (January 2022) is advisory, but it shows what inspectors look for. The 2023 Regulations add binding rules, for example no glass facades in schools.

  • At least two staircases, internal stairs at least 1.5 m wide, treads of 300 mm and risers up to 150 mm preferred.
  • Any room for over 45 people needs two doorways. Pre-school, kindergarten and class 1 rooms belong at ground level or the level of exit discharge.
  • Exit doors use panic bars, except doors from classrooms straight outside.
  • Travel distance is limited to 30 m (Type 1 and 2 construction) or 22.5 m (Type 3 and 4), increased by 50 percent where sprinklered.
  • Fire compartments of 750 m² with 120-minute barriers.
  • Access control must unlock on alarm, sprinkler activation or power loss.
  • Emergency lighting within 5 seconds, lasting at least 90 minutes, with green exit signs.
  • Laboratories and kitchens: flammable stock only in labs, LPG pipelines in separate external shafts, and no LPG kitchens in basements.

Fixed installations by building height

The handbook reproduces the NBC 2016 Table 7 for educational buildings. Treat it as a guide and confirm with the checklist the portal shows for your category.

BuildingInstallationsWater storage
Under 15 m, G+1 or moreExtinguishers and first-aid hose reel. Sprinklers only if the basement is over 200 m²Terrace tank 10,000 L (plus 5,000 L if basement over 200 m²)
15 to 24 mAdds a down-comer and a manual alarm with talk-back and public addressTerrace tank 25,000 L
Above 24 m to 30 mWet riser and yard hydrant replace the down-comer; manual alarm continuesUnderground tank 50,000 L (plus 5,000 L if basement over 200 m²)

That table shows automatic detection as not required for schools, while the handbook text says to provide an alarm system. The portal checklist for your category settles which applies.

Renewal and who can do it

The first certificate is valid for three years, then renewals run two years with six-monthly inspection reports. An Enrolled Fire Safety Officer must be appointed in the two months before expiry. For educational buildings from 9 to 15 m a General, Advanced or Specialist officer can renew; from 15 to 30 m it needs Advanced or Specialist. See Fire Safety Officer grades and the renewal guide.

Why coaching classes are in scope

On 24 May 2019 a fire at the Takshashila Arcade in Sarthana, Surat killed 22 students. A coaching centre was running from a makeshift dome on the terrace, reachable only by a wooden staircase that the fire destroyed, with no fire safety equipment. The State ordered coaching centres shut until inspected and ordered inspections of schools, colleges, hospitals and malls. In June 2026 Surat began a school audit after fires elsewhere in India.

Common questions

Does a coaching class in Gujarat need a fire safety certificate?

Coaching classes, pre-schools and training centres above 9 m are named in the renewal table, and educational buildings of 9 m and above fall in the Third Schedule. Smaller premises may be covered through other categories, so confirm with the portal checklist or your fire authority.

Who must be present in a large school for fire safety?

The Regulations require a Fire Safety Executive for educational buildings of 15 m and above, or with more than 5,000 students.

How many exits must a classroom have?

The GIDM handbook advises two doorways for any room used by more than 45 people, and at least two staircases in the building. Check your own category checklist.

More questions? See the fire safety FAQ for short answers on certificates, renewal, penalties, extinguishers and pandals.

Equipment for schools and classes

Munshi Fire Safety supplies extinguishers, refilling, inspection and annual maintenance for educational premises in Vapi and South Gujarat. Equipment does not by itself make a building compliant.

Sources

Facts last verified on 13 November 2026.

This guide is general information, not legal advice. Rules, forms and fees change, and the Gujarat Fire Safety Compliance Portal prevails over any summary. Confirm your case with the fire authority, a Licensed Agency or a lawyer before you act.