Fire Safety for Godowns, Warehouses, Hazardous Storage and Car Parks in Gujarat
Storage buildings need a Gujarat Fire Safety Certificate when any floor is over 500 m². Hazardous buildings and multilevel car parks need one at any size. Storage and hazardous buildings above 15 m are not permitted, and renewal is by a Specialist grade Fire Safety Officer from small built-up areas.
- Storage
- Any floor over 500 m²
- Hazardous buildings
- All
- Multilevel car parks
- All
- Height limit
- Storage and hazardous: not above 15 m
Thresholds and renewal grades
| Use | Certificate needed when | Renewal |
|---|---|---|
| Storage and warehouses | Any floor over 500 m² (the checklists use covered area over 250 m²) | Built-up area over 250 m²: Specialist |
| Hazardous buildings | All | Built-up area over 100 m²: Specialist |
| Multilevel car parks | All | Specialist |
Storage and hazardous buildings above 15 m are not permitted (car parks are the exception). Where the Third Schedule and the Regulation tables differ, as they do for storage at 500 m² of floor against 250 m² of covered area, the checklist category decides what the portal asks for. A Fire Safety Executive is needed for storage and hazardous buildings that are not under the Factories Act and, for storage, are below 15 m at G+1 or more.
Rules specific to storage
- Section 22 of the Act lets fire officers direct removal, and seize or detain, goods likely to cause a fire risk after notifying the occupier. The hearing can be dispensed with where danger is imminent.
- Substations and oil-filled transformers stay out of buildings.
- Boilers sit in 4-hour rooms on the periphery, never in a basement.
- Multilevel car parks need at least two ramps at 1:15, a Fire Safety Executive and a Specialist renewal.
Hazardous goods and other laws
Sites storing hazardous chemicals, petroleum or gas can also fall under the MSIHC Rules, 1989 or under PESO, which have their own plans, licences and drills. The Gujarat fire certificate does not replace those.
Common questions
What size of warehouse needs a fire certificate in Gujarat?
Under the Third Schedule, any floor over 500 m². The portal checklists use covered area over 250 m², so confirm on the portal.
Can officers remove goods from a godown?
Yes. Section 22 of the Act lets fire officers direct removal, or seize or detain, goods that are a fire risk after notifying the occupier.
Do multilevel car parks need a certificate?
Yes, all multilevel car parks, with a Specialist grade officer for renewal.
More questions? See the fire safety FAQ for short answers on certificates, renewal, penalties, extinguishers and pandals.
Equipment for storage sites
Munshi Fire Safety supplies extinguishers, hydrant parts and maintenance contracts for godowns and warehouses in South Gujarat. Equipment does not by itself make a site compliant.
Sources
- Gujarat Government Gazette Extraordinary, Extra No. 298, 23 October 2026, Part IV-B: notification No. GH/V/198 of 2026, Gujarat Fire Prevention and Life Safety Measures (Amendment) Rules, 2026
- Gujarat Fire Prevention and Life Safety Measures Regulations, 2023 (Gazette Extraordinary, 13 December 2023), amended 24 June 2024
- Gujarat Fire Prevention and Life Safety Measures Act, 2013 (Guj. 11 of 2013), as amended in 2021
- Gujarat Fire Safety Compliance Portal (gujfiresafetycop.in)
Facts last verified on 13 November 2026.
This guide is general information, not legal advice. Rules, forms and fees change, and the Gujarat Fire Safety Compliance Portal prevails over any summary. Confirm your case with the fire authority, a Licensed Agency or a lawyer before you act.