Fire Safety Compliance Calendar for Gujarat Buildings
The Gujarat fire safety cycle runs on a fixed calendar: the certificate is valid for three years, annual declarations fall within 15 days of the end of years one and two, the renewal starts at least two months before expiry, and after each renewal there is a six-monthly inspection report and two emergency mock drills a year. Late filings are charged in blocks of 90 days.
- Certificate
- 3 years, then 2-year renewals
- Renewal
- Start 2 months before expiry
- Inspection report
- Every 6 months after renewal
- Mock drills
- Twice a year
The statutory calendar
| When | What | Source |
|---|---|---|
| Before development permission | Fire Safety Plan Approval (FSPA), decided within 21 days | Regulation 5 |
| Before occupation | Fire Safety Certificate Approval (FSCA) in Form B14, with self-certifications on no alteration, AMC and electrical safety. Valid 3 years | Regulation 5, Rule 24 |
| Within 15 days of completing year 1 and year 2 | Annual declaration (Form B2) by the Licensed Agency, or the owner if no agency is appointed | Rule 26 |
| At least 2 months before expiry | Appoint a Fire Safety Officer and apply for renewal | Section 12, Rule 25 (2024 amendment), Regulation 7 |
| At renewal | FSO inspection and renewal in Form B13.3, valid 2 years | Rule 25 |
| Every 6 months after renewal | Declaration cum inspection report (Form B15) uploaded by the FSO | Rule 26 |
| Twice a year | Emergency mock drill, with a record kept | Fourth Schedule, Annexures 11 and 12 |
| Late filing | Late fee charged in blocks of 90 days | Regulation 11 |
| After a rejection | Appeal to the Director within 15 days, with 50% of the fee | Regulation 11 |
The renewal steps are in our renewal guide, with a date calculator. Late fee amounts are in the fee calculator.
Inside the building: an indicative routine
Gujarat law fixes the certificate cycle but not a day-by-day schedule. The routine below is good practice drawn from summaries of IS 2190 and from practitioner guides. It is not a legal requirement, so adapt it to the manufacturer's manual, your annual maintenance contract (AMC), the Regulations and your fire authority.
- Daily or weekly: exits and escape routes clear and unlocked; extinguishers in place; alarm panel reading normal; pump room and hydrant areas accessible.
- Monthly: visual inspection of extinguishers (location, access, pressure gauge, damage); hydrant and hose reel checks.
- Annually: detailed extinguisher maintenance by a trained person, and the AMC service of fire protection systems.
- Every few years: extinguisher hydrostatic testing. Summaries of IS 2190 give 3 years for water, foam and dry powder types and 5 years for CO2 and clean agent types, and Gujarat's own Fire Safety Officer inspection checklist refers to the same intervals.
- Emergency lighting: the 2023 Regulations require it to come on within 5 seconds of failure and run for at least 1 hour 30 minutes.
Keep a register
Keep a register for each extinguisher with its location, type, capacity, manufacturer and the dates of service, test and refill, and keep it ready for the fire department. Keep the certificate, the renewal in Form B13.3, the six-monthly reports, the drill records and the AMC together in one file.
Common questions
How often are mock drills required in Gujarat?
Emergency mock drills are held twice a year by the Fire Safety Officer after each renewal, with a record kept (Fourth Schedule, Annexures 11 and 12).
What is the annual declaration (Form B2)?
A declaration by the Licensed Agency, or by the owner, occupier or developer if no agency is appointed, that the fire safety measures are operational. It is filed within 15 days of completing the first and second year of the certificate.
How often should extinguishers be inspected?
Summaries of IS 2190 describe monthly visual inspection and annual maintenance by a trained person, with periodic hydrostatic testing. Follow the manufacturer's manual and your AMC.
More questions? See the fire safety FAQ for short answers on certificates, renewal, penalties, extinguishers and pandals.
An AMC that fits the calendar
The certificate application asks for an annual maintenance contract for the fire protection equipment. Munshi Fire Safety services extinguishers, hydrant systems and alarms across Vapi, Valsad, Daman, Silvassa and South Gujarat.
Sources
- Gujarat Fire Prevention and Life Safety Measures Rules, 2014, with amendments to 2026
- Gujarat Fire Prevention and Life Safety Measures Regulations, 2023 (Gazette Extraordinary, 13 December 2023), amended 24 June 2024
- Gujarat Fire Prevention and Life Safety Measures Act, 2013 (Guj. 11 of 2013), as amended in 2021
- Gujarat Fire Safety Compliance Portal (gujfiresafetycop.in)
Facts last verified on 13 November 2026.