Residential buildings of 15 m and above need a Fire Safety Certificate in Gujarat. Where several people occupy a building, the registered society or association is responsible for providing and maintaining the measures. The certificate runs three years, then renews every two years with six-monthly inspection reports and mock drills.

Certificate needed
15 m and above
First certificate
Valid 3 years
Renewal
Every 2 years, six-monthly reports
Fire Safety Executive
60 m and above

Who is responsible

Section 18 of the Act puts the duty on the owner or the registered society or association. In a building with several occupiers, Rule 26(5) makes the society or association responsible. The managing committee should therefore treat the certificate calendar as a standing agenda item.

The society calendar

  1. First certificate: valid three years.
  2. Years one and two: annual declaration (Form B2) within 15 days of completing each year.
  3. At least two months before expiry: appoint an Enrolled Fire Safety Officer and apply for renewal.
  4. Renewal: FSO inspection and renewal in Form B13.3, valid two years.
  5. Every six months afterwards: declaration cum inspection report (Form B15) uploaded by the FSO.
  6. Twice a year: emergency mock drill with a record kept.

Self-certifications at the FSCA stage cover no alterations, an AMC for fire equipment and safe electrical installation. See the compliance calendar and renewal guide.

Who can renew a residential certificate

Building heightFire Safety Officer grade
15 to 25 mGeneral, Advanced or Specialist
25 to 45 mAdvanced or Specialist
Above 45 mSpecialist

Residential buildings of 60 m and above also need a Fire Safety Executive. The portal checklists split flats into the bands 15 to 35 m, 35 to 45 m, 45 to 60 m and 60 m to under 100 m.

Tower features in the 2023 Regulations

  • Hollow-plinth parking sprinklered to IS 15105 for buildings 15 to 70 m.
  • Stair width of 2 m from 25 m.
  • One fire lift per 1,200 m².
  • Refuge area at about every 18 m of height.
  • Fire check floor above 70 m, with fire drenchers on its edge.
  • 900 V grade wiring above 45 m.
  • Auto-glow signage for the 45 to 70 m band.
  • Emergency route plans framed on every floor, and Class 1 flame-spread interior finishes.

What committees can do now

  • Keep a dated register of extinguishers, hose reels and pumps.
  • Put an annual maintenance contract in writing and keep the service reports.
  • Run and record two mock drills a year, and keep escape routes and the refuge area clear.
  • Calendar the FSO appointment for the two months before expiry.

Common questions

Is the housing society or the builder responsible for the fire certificate?

For an occupied building with several occupiers, Rule 26(5) makes the registered society or association responsible for providing and maintaining the fire measures.

What height of residential building needs a fire certificate in Gujarat?

Residential buildings of 15 m and above, which is the Gujarat high-rise threshold.

How often must a society run a fire drill?

The Regulations call for two emergency mock drills a year under the Fire Safety Officer, with the checklists in Annexures 11 and 12.

More questions? See the fire safety FAQ for short answers on certificates, renewal, penalties, extinguishers and pandals.

Equipment and AMC for societies

Munshi Fire Safety supplies extinguishers, hydrant parts and signage and offers maintenance contracts for societies in Vapi and South Gujarat. Ask what documentation comes with each service visit.

Sources

Facts last verified on 13 November 2026.

This guide is general information, not legal advice. Rules, forms and fees change, and the Gujarat Fire Safety Compliance Portal prevails over any summary. Confirm your case with the fire authority, a Licensed Agency or a lawyer before you act.