Fire Safety Rules for Pandals and Temporary Structures in Gujarat
In Gujarat, the organiser of a pandal, mandap, shamiyana or tent must display a declaration (Form C1) at least 48 hours before use and file the online checklist, with a fee of Rs 2,000. Since 23 October 2026, Rule 27 requires the structure to meet IS 8758 and the section 58 regulations on access, open space, exits, materials, first-aid fire-fighting, water, wiring and trained staff.
- Declaration
- Form C1, 48 hours before use
- Online checklist fee
- Rs 2,000
- Open margin
- 4.5 m on all sides
- Exit width
- At least 2.5 m
- Water barrel
- 200 litres, plus sand and water buckets within 50 m
What is covered
Section 27 of the Act, Regulations 13 and 14, and Rule 27 (as replaced on 23 October 2026) apply to temporary structures such as mandaps, shamiyanas, tents and pandals. That covers festival pandals such as those for Navratri and Ganesh Chaturthi, wedding marquees, exhibitions, trade shows, camps and public gatherings. The duty falls on the promoter, organiser, owner or occupier.
Before the event
- Display a declaration (Form C1) at a prominent place at least 48 hours before the structure is used.
- File the online checklist on the portal with a fee of Rs 2,000.
- For public gatherings, prepare a layout plan and stall details. Above 500 m², an electrical engineer's certificate with photograph is also needed.
Standards the structure must meet
| Requirement | Figure or rule |
|---|---|
| Material | Fire-resistant |
| Exits | Two emergency exits or two open sides; exit width at least 2.5 m |
| Ceiling height | At least 3 m |
| Open margin | 4.5 m on all sides |
| Electrical lines | Nothing under live electrical lines |
| Hazards | 15 m clear of railway lines, substations and furnaces |
| Kitchens | 15 m away, built with tin sheets |
| Water | A 200 litre water barrel, plus water and sand buckets, within 50 m |
| Extinguishers | Water, dry powder and CO2 extinguishers at strategic points |
| Wiring | In PVC conduits with MCB or ELCB |
| Standby power | A standby generator for pandals over 500 m² |
These figures come from the 2023 Regulations. Rule 27 now names nine matters the structure must satisfy: access; open space around the structure; distance from medium and high voltage electrical wires and hazardous installations; means of exit; material of construction; first-aid fire-fighting arrangements; water storage for fire-fighting; electrical wiring; and availability of trained fire-fighting staff.
Which edition of IS 8758
Rule 27 as notified on 23 October 2026 refers to IS 8758:1993, the BIS standard on fire precautionary measures for temporary structures. Our reading of the 2023 Regulations refers to the same standard with a 2013 edition. Ask the fire authority which edition it applies to your event.
If you do not comply
The fire authority can inspect, give directions, and then seal or dismantle the structure at the defaulter's cost. Fines of up to Rs 1,00,000 and Rs 1,000 per day for continuing disobedience are provided for. A false declaration is an offence. Failing to comply with directions about temporary structures is also an offence under section 39(1) of the Act. See penalties.
Organiser checklist
- Confirm the layout: two exits or two open sides, exits at least 2.5 m wide, a 4.5 m margin all around.
- Walk the site for overhead electrical lines, and measure distances to railway lines, substations, furnaces and cooking areas.
- Check the materials are fire-resistant and the wiring is in PVC conduit with MCB or ELCB.
- Place water, dry powder and CO2 extinguishers at strategic points, with the 200 litre barrel and buckets within 50 m. Buy extinguishers that carry the ISI mark.
- Arrange trained fire-fighting staff for the event.
- Post Form C1 at least 48 hours before use, and file the online checklist with the Rs 2,000 fee.
Common questions
Does a wedding pandal need fire clearance in Gujarat?
The rules cover mandaps, shamiyanas, tents and pandals. The organiser must display Form C1 at least 48 hours before use and file the online checklist with the Rs 2,000 fee, and the structure must meet the standards above.
How early must the Form C1 declaration be displayed?
At least 48 hours before the structure is used, in a prominent place.
How many extinguishers does a pandal need?
The Regulations ask for water, dry powder and CO2 extinguishers at strategic points, plus a 200 litre water barrel with water and sand buckets within 50 m. They do not fix a number in the text we have read, so ask the fire authority how many it expects for your layout.
More questions? See the fire safety FAQ for short answers on certificates, renewal, penalties, extinguishers and pandals.
Extinguishers for your event
Munshi Fire Safety supplies extinguishers and fire safety equipment from Vapi. Tell us the size and layout of your event and the equipment you plan to place.
Sources
- Gujarat Government Gazette Extraordinary, Extra No. 298, 23 October 2026, Part IV-B: notification No. GH/V/198 of 2026, Gujarat Fire Prevention and Life Safety Measures (Amendment) Rules, 2026
- Gujarat Fire Prevention and Life Safety Measures Act, 2013 (Guj. 11 of 2013), as amended in 2021
- Gujarat Fire Prevention and Life Safety Measures Regulations, 2023 (Gazette Extraordinary, 13 December 2023), amended 24 June 2024
- Gujarat Fire Safety Compliance Portal (gujfiresafetycop.in)
Facts last verified on 13 November 2026.
This guide is general information, not legal advice. Rules, forms and fees change, and the Gujarat Fire Safety Compliance Portal prevails over any summary. Confirm your case with the fire authority, a Licensed Agency or a lawyer before you act.