Gujarat Fire Safety Rules 2026 Amendment: What Changed
On 23 October 2026 the Government of Gujarat notified the Gujarat Fire Prevention and Life Safety Measures (Amendment) Rules, 2026 (No. GH/V/198 of 2026). They came into force when they were published in the Gazette. The amendment replaces the Third Schedule, the list of buildings that need a fire safety certificate, and replaces Rules 2(2), 22 and 27. Industrial buildings come under the new Schedule from 1 April 2027.
- Notification
- GH/V/198 of 2026
- Published
- 23 October 2026, Gazette Extra. No. 298
- In force
- On publication
- Industrial buildings
- From 1 April 2027
- Fees, penalties, validity
- No change in this notification
What the notification changes
The notification amends the Gujarat Fire Prevention and Life Safety Measures Rules, 2014 in four places:
- Rule 2(2): words not defined in the Rules take their meaning from the Act, the Gujarat development control regulations (GDCR), the regulations made under section 58 of the Act, or the relevant Bureau of Indian Standards (BIS) standards.
- Rule 22: minimum standards for fire prevention and life safety in buildings and premises, with new powers for the Director, the fire officers and the Government (see below).
- Rule 27: minimum standards for temporary structures such as mandaps, shamiyanas, tents and pandals.
- The Third Schedule: the list of buildings that need a certificate of compliance, replaced in full.
The Government used the proviso to section 57(1) of the Act, which allows rules to be made without prior publication where immediate action is needed. That is why the rules took effect on the day they were published.
The new Third Schedule: who needs a certificate
The following buildings require a certificate of compliance for fire prevention, life safety and fire protection:
| Building | When a certificate is needed |
|---|---|
| High-rise buildings | Height of 15 m and above, except occupancies or buildings particularly excluded from the Schedule |
| Hotel, educational, institutional, business, mercantile, storage, hazardous and mixed-occupancy buildings | Built-up area of more than 500 m² on any one or more floors cumulatively |
| Educational buildings | Height of 9 m and above |
| Institutional buildings (hospitals, nursing homes and mental institutions with beds, with or without ICU) | Height of 9 m and above |
| Assembly buildings | All |
| Multilevel car parking | All |
| Buildings with incidental assembly occupancy | More than 300 m² on any floor |
| Basements | Two or more basements, or one basement of more than 500 m² |
| Fuelling stations | All |
| Industrial: low hazard | Built-up area of more than 500 m², from 1 April 2027 |
| Industrial: moderate hazard | Built-up area of more than 500 m², from 1 April 2027 |
| Industrial: high hazard | Built-up area of more than 50 m², from 1 April 2027 |
Note 4 of the Schedule says that for the industrial categories, the provisions come into force on 1 April 2027. Note 1 says the terms used in the Schedule have the meaning given in the regulations made under section 58 of the Act. Note 3 advises owners and occupiers to provide and maintain the fire-fighting, life safety and fire protection installations listed in those regulations at all times.
For a plain-language walk through the triggers, read who needs a fire safety certificate in Gujarat.
What is new compared with the 2021 Schedule
The notification does not publish a change list. Comparing the 2026 text with the Third Schedule substituted in 2021, as we read both, these are the differences:
- Fuelling stations are named. "All fuelling stations" is now a listed category. Petrol pumps and gas stations were already a fee category on the portal in 2022, so what is new is that they now appear in the Schedule itself.
- Industrial low-hazard buildings are caught at more than 500 m² built-up area. The 2021 text caught light-hazard industrial buildings at a height of 15 m and above.
- The separate line "all hazardous buildings" is not in the 2026 Schedule. Hazardous buildings are still listed, in the category of buildings with more than 500 m² built-up area.
- The note about the Factories Act is gone. The 2021 Schedule said light-hazard industrial buildings below 15 m were covered by the Factories Act, 1948. The 2026 Schedule does not repeat it.
- Definitions now point to the section 58 regulations instead of Part 4 of the National Building Code 2016.
- The industrial categories have a start date, 1 April 2027.
The thresholds for high-rise buildings, educational and institutional buildings, assembly buildings, car parking, incidental assembly and basements read the same in both versions.
Rule 22: minimum standards and new powers
Rule 22 applies the minimum standards in the GDCR and the section 58 regulations to 19 matters: access to the building; number, width, type and arrangement of exits; protection of exits by fire check doors or pressurisation; compartmentation; smoke management; fire extinguishers; first-aid hose reels; automatic fire detection and alarm; public address system; automatic sprinklers; internal and yard hydrants; pumping arrangements; captive water storage; exit signage; lifts; standby power; refuge area; fire control room; and special fire protection for special risks.
The rule also gives three powers:
- Where the building regulations give no fire measures for a class of occupancy, the Director may require the owner or occupier to provide measures that follow international standards specified by the Fire Prevention Wing.
- The Government may, by order and with written reasons, relax, modify or annul a requirement for a class of occupancy in special areas, or for buildings built or under construction before 23 October 2026.
- The Regional Fire Officer or Chief Fire Officer may, with written reasons, require an owner or occupier to provide additional fire prevention and fire safety measures.
Rule 27: pandals, mandaps, shamiyanas and tents
Rule 27 says temporary structures must meet IS 8758:1993 and the section 58 regulations on nine matters: access, open space around the structure, distance from medium and high voltage electrical lines and hazardous installations, exits, construction material, first-aid fire-fighting, water storage, electrical wiring, and trained fire-fighting staff. The promoter, organiser, owner or occupier must provide and maintain these measures. More in our guide to fire safety rules for pandals and temporary structures.
What the notification does not say
- It does not change fees, penalties or validity periods.
- It does not define "fuelling station". Ask the fire authority whether a CNG station or an EV charging station is treated as one.
- It sets no transition date for buildings other than industrial ones.
- It does not say how the portal checklists will change. The portal prevails over the Regulations if its formats differ (Regulation 30), so check the checklist for your building category on the portal.
What owners can do now
- Check your building against the table above using the height and built-up area in your sanctioned plan.
- If you run an industrial unit, work out its hazard class and built-up area now, and plan for 1 April 2027.
- Look up your category on the portal and read its checklist.
- Walk through your fire protection equipment. Extinguishers on sale in India need the ISI mark (see how to check the ISI mark), and a certificate application asks for a self-certification that an annual maintenance contract is in place.
- For the application itself, you will work with the fire authority, a Licensed Agency and, at renewal, a Fire Safety Officer. See the three-step certificate process.
Common questions
Is the 2026 amendment already in force?
Yes. Rule 1(2) says the amendment rules come into force on the date of their publication in the Official Gazette, which was 23 October 2026. For industrial buildings, Note 4 of the new Third Schedule sets 1 April 2027.
Do petrol pumps now need a fire safety certificate in Gujarat?
The new Third Schedule lists "all fuelling stations" with no area or height threshold. Petrol pumps and gas stations were already a fee category on the portal in 2022, so the change is that they are named in the Schedule. The notification does not define the term, so ask the fire authority about CNG and EV charging stations.
Does my factory need a certificate under the new rules?
If it is an industrial building with low or moderate hazard and more than 500 m² built-up area, or high hazard and more than 50 m², the Schedule lists it, from 1 April 2027. The hazard class is defined in the regulations made under section 58 of the Act, so confirm it with a Fire Safety Officer, a Licensed Agency or the fire authority.
Did the amendment change fees or penalties?
Not in this notification. It contains no change to fees, penalties or validity periods.
More questions? See the fire safety FAQ for short answers on certificates, renewal, penalties, extinguishers and pandals.
Get your equipment ready
Whatever your building category, the certificate process looks at working extinguishers, hydrants, alarms and signage, and an annual maintenance contract. Munshi Fire Safety supplies and services this equipment from Vapi. Certificate applications themselves go through the fire authority, a Licensed Agency and a Fire Safety Officer.
Sources
- Gujarat Government Gazette Extraordinary, Extra No. 298, 23 October 2026, Part IV-B: notification No. GH/V/198 of 2026, Gujarat Fire Prevention and Life Safety Measures (Amendment) Rules, 2026
- Gujarat Fire Prevention and Life Safety Measures Rules, 2014, with amendments to 2026
- Gujarat Fire Safety Compliance Portal (gujfiresafetycop.in)
Facts last verified on 13 November 2026.