Fire Extinguisher Inspection, Refilling and Testing Schedule in India
A commonly followed schedule based on IS 2190 is a monthly visual check, yearly maintenance by a trained person, and a hydrostatic test every 3 years for water, foam and dry powder types and every 5 years for CO2 and clean agent types. A cylinder that fails is destroyed, not refilled. The 3-year and 5-year test intervals also appear in the Gujarat Fire Safety Officer inspection checklist.
- Visual check
- Monthly
- Maintenance
- Yearly, by a trained person
- Hydrostatic test
- 3 years (water, foam, dry powder)
- Hydrostatic test, CO2 and clean agent
- 5 years
The schedule
| When | What |
|---|---|
| Monthly | Visual inspection of location, access, pressure gauge, seals and damage |
| Yearly | Detailed maintenance by a trained person, with discharge or recharge as needed |
| Every 3 years | Hydrostatic test: water, foam and dry powder types |
| Every 5 years | Hydrostatic test: CO2 and clean agent types |
The Gujarat Fire Safety Officer inspection checklist (IN4.1 in the 2022 Applicant Guide) confirms the 3-year and 5-year hydrostatic test intervals. The monthly and yearly rhythm follows summaries of IS 2190:2010; always follow the manufacturer's manual, your maintenance contract and the fire authority. Do not mix in US intervals from NFPA 10, which differ.
Keep an extinguisher register
Keep a register with location, type, capacity, manufacturer and date, plus service, test and refill dates, ready for the fire department. A dated register is one of the records inspectors ask for.
Refilling and the ISI mark
The 2023 quality control order makes the ISI mark compulsory for portable and wheeled extinguishers. Sale and stocking rules come from section 17 of the BIS Act, 2016. The order itself is silent on refilling and servicing of older units. See how to check the ISI mark.
The wider routine in a building
Gujarat law fixes the certificate cycle, not a day-by-day schedule. The routine below is indicative good practice from IS 2190 summaries and practitioner guides, so adapt it to the manufacturer's manual, your AMC and the fire authority.
- Daily and weekly: exits clear and unlocked, alarm panel normal, extinguishers in place, pump room accessible.
- Monthly: hydrant and hose reel checks, diesel pump fuel and battery, sprinkler valves open and sealed.
- Quarterly: a rotating sample of detectors and call points tested, fire pump run, fire door and emergency light sample.
- Half-yearly and annual: AMC service, full alarm test, pump flow test and a full 90-minute emergency light discharge test.
Common questions
How often should fire extinguishers be serviced in India?
A common schedule is a monthly visual check and yearly maintenance by a trained person, with a hydrostatic test every 3 years for water, foam and dry powder types and every 5 years for CO2 and clean agent types.
What happens to an extinguisher that fails a pressure test?
It is destroyed, not refilled.
What records should I keep for extinguishers?
A register with location, type, capacity, manufacturer, and service, test and refill dates.
More questions? See the fire safety FAQ for short answers on certificates, renewal, penalties, extinguishers and pandals.
Refilling and annual maintenance
Munshi Fire Safety offers extinguisher refilling, inspection and annual maintenance from Vapi. Ask for dated service records with each visit.
Sources
- Applicant Guide, first edition 2022, Gujarat Fire Safety Compliance Portal (fee table and late-fee illustrations)
- Gazette of India Extraordinary, Fire Extinguishers (Quality Control) Order, 2023, S.O. 3585(E), 9 August 2023
- Bureau of Indian Standards
- IS 2190:2010 as summarised in public tender notices and practitioner guides (standard text not read; confirm with BIS)
Facts last verified on 13 November 2026.