Fire Safety Rules for Hospitals and Nursing Homes in Gujarat
Hospitals and nursing homes with beds need a Gujarat Fire Safety Certificate from 9 m. Renewal is by a General, Advanced or Specialist Fire Safety Officer below 15 m, Advanced or Specialist from 15 to 24 m, and Specialist only above 24 m. A Fire Safety Executive is needed from 15 m. Courts have repeatedly pushed hospital fire audits since 2020.
- Certificate needed
- 9 m and above
- Renewal above 24 m
- FSO Specialist
- Fire Safety Executive
- 15 m and above
- Emergency lighting
- Within 5 seconds, 90 minutes
Building rules for hospitals
From the GIDM hospital handbook (January 2022, advisory) and the 2023 Regulations:
- At least two staircases; internal stairs at least 2 m wide; corridors where patients are moved at least 2.4 m, other corridors at least 1.5 m; exit width from patient sections at least 2 m.
- Travel distance 30 m or 22.5 m (50 percent more if sprinklered). Dead ends no longer than 6 m.
- Operation theatres, delivery rooms, ICUs and recovery rooms separated by 120-minute fire and smoke barriers; floors compartmented at 1,800 m².
- ICU preferably at ground level, sprinklered, with an alternate exit wide enough to roll beds.
- Progressive horizontal evacuation for patients who cannot self-evacuate.
- No glass facade (Regulation 15.33.2). Fire-retardant curtains, bedsheets and claddings.
- Fire command centre on the entrance floor with the alarm panel and public address.
- Oxygen: staff must know where the shut-off valve is. Gas manifolds ventilated, and LPG kitchens never in basements.
Fixed installations and water tanks
For buildings with beds, the handbook reproduces NBC 2016 Table 7. Confirm against the portal checklist for your category.
| Building | Installations | Underground tank |
|---|---|---|
| Under 15 m, plot up to 1,000 m², up to G+1 | Extinguishers, hose reel, manual alarm. Sprinklers only if basement over 200 m² | Terrace tank 5,000 L |
| Under 15 m, plot up to 1,000 m², G+2 or more | Adds wet riser, sprinklers and automatic detection | 75,000 L, terrace 10,000 L |
| Under 15 m, plot over 1,000 m² | Adds yard hydrant | 1,00,000 L, terrace 10,000 L |
| 15 to 24 m | Same set | 1,50,000 L, terrace 20,000 L |
| Above 24 m to 45 m | Same set | 2,00,000 L, terrace 20,000 L |
The NABH advisory for accredited hospitals uses a different minimum table (sprinklers and a manual alarm even under 15 m up to G+1). The two documents have different purposes. For the Gujarat certificate, the statutory checklist for the category governs.
Renewal and officers
Renewal by an enrolled Fire Safety Officer follows the usual FSPA, FSCA and FSCR cycle. Under 15 m a General, Advanced or Specialist officer can renew. From 15 to 24 m it needs Advanced or Specialist, and above 24 m only a Specialist can renew. Hospitals of 15 m and above need a Fire Safety Executive on the premises. See Fire Safety Officer grades.
The legal and court trail
- After the Shrey Hospital fire in Ahmedabad (August 2020, eight Covid patients died) and the Uday Shivanand Hospital fire in Rajkot (five died), the Supreme Court in December 2020 ordered fire safety audits of hospitals nationwide.
- On 15 December 2020 the Gujarat High Court told the State to enact a consolidated code or guidelines on fire safety for clinical establishments and to frame rules for ICU fire safety. It also ordered strict compliance with the 2013 Act in hospitals, nursing homes and school buildings in Ahmedabad.
- In May 2021 a fire in an ICU at a Bharuch hospital killed 16 Covid patients and two nurses. The Union Home Secretary then wrote to all states asking them to re-inspect hospitals and nursing homes.
NABH-accredited hospitals are also expected to hold a valid fire NOC, mock drill records and maintenance plans. See fire safety audits compared.
Common questions
Does a small nursing home need a fire safety certificate in Gujarat?
Hospitals and nursing homes with beds are in the Third Schedule from 9 m. Check the portal checklist for the category and your height and plot size.
Who can renew a hospital fire certificate above 24 m?
Only a Fire Safety Officer of the Specialist grade.
How long must hospital emergency lighting last?
Emergency lighting must come on within 5 seconds and last at least 90 minutes under the GIDM handbook and the Regulations.
More questions? See the fire safety FAQ for short answers on certificates, renewal, penalties, extinguishers and pandals.
Equipment and maintenance for hospitals
Munshi Fire Safety supplies extinguishers, refilling, inspection and maintenance contracts for clinical premises in South Gujarat. We do not certify buildings or issue fire certificates.
Sources
- Gujarat Fire Prevention and Life Safety Measures Regulations, 2023 (Gazette Extraordinary, 13 December 2023), amended 24 June 2024
- Gujarat Fire Prevention and Life Safety Measures Rules, 2014, with amendments to 2026
- Gujarat Institute of Disaster Management (GIDM), Handbook Series on Fire Safety: Hospital Buildings and Educational Buildings (January 2022; advisory)
- NABH Revised Advisory for Minimum Essential Fire Safety Measures, 20 September 2022
- Gujarat Fire Safety Compliance Portal (gujfiresafetycop.in)
Facts last verified on 13 November 2026.
This guide is general information, not legal advice. Rules, forms and fees change, and the Gujarat Fire Safety Compliance Portal prevails over any summary. Confirm your case with the fire authority, a Licensed Agency or a lawyer before you act.